Section 22 - System Communication
22–3
The Ademco Contact ID reporting format comprises a 10-digit subscriber account number, 1-
digit event qualifier (“new” or “restore”), 3-digit event code, and 3-digit zone number, user
number, or system status number, as follows:
Ademco Contact ID Reporting
takes the following format:
CCCCCCCCCC Q EEE ZZZ
where:
CCCCCCCCCC = Customer ID (subscriber account number)
Q = Event qualifier, where: E = new event, R = restore
EEE = Event code (3 hexadecimal digits)*
ZZZ = Zone/contact ID number reporting the alarm, or user number for open/close
reports. System status messages (AC Loss, Walk Test, etc.) contain zeroes
in the ZZZ location.
*
NOTE:
For a complete list of event codes, refer to the Central Station office receiver
manual.
TABLE OF CONTACT ID EVENT
CODES
Code Definition
100 Alarm, 24-hour, Medical
110 Fire Alarm
121 Duress
122 Alarm, 24-hour Silent
123 Alarm, 24-hour Audible
131 Alarm, Perimeter
132 Alarm, Interior
134 Alarm, Entry/exit
135 Alarm, Day/Night
143 Alarm, Expansion Module
146 Silent Burglary
150 Alarm, 24-Hour Auxiliary
162 Alarm, 24-Hour, Carbon Monoxide Det.
301 AC Power
302 Low System Battery/Battery Test Fail
305 System Reset
321 Bell/Siren # 1 Trouble
333 Trouble or Tamper Expansion Module
344 RF Receiver Jam Detection
351 Telco Line Fault
Code Definition
353 Long Range Radio Trouble
373 Fire Loop Trouble
374 Exit Error Alarm
380 Global Trouble, Trouble Day/Night
381 RF Supervision Trouble
383 RF Sensor Tamper
384 RF Sensor Low Battery
401 Disarmed, Armed AWAY (Max), Armed
AWAY
406 Cancel by User
407 Remote Arm/Disarm (Downloading)
408 Quick Arm AWAY/MAX
441 Disarmed/Armed STAY/INSTANT, Quick
Arm STAY/INSTANT
570 Bypass
602 Periodic Test
606 AAV to Follow
607 System Test
623 Event Log 80% Full
629 1-1/3 Day No Event
Comentários a estes Manuais