AUX. POWER
OUTPUT
10.5-13.8VDC
600mA MAX.
(500mA MAX.
FOR UL
INSTALLATIONS)
INTERRUPTS
FOR 4-WIRE
FIRE ALARM
RESET.
ALL CIRCUITS
ARE POWER
LIMITED.
NOTE:
KEYPAD(S)
CURRENT AND
ALL OTHER
DEVICES
DRAWING
POWER FROM
TERMS 4 & 5
MUST BE
INCLUDED IN
AUX CURRENT
DRAIN
CALCULATIONS.
OPTIONAL
FOR UP TO 30 ADDITIONAL ZONES
(ONE FROM EITHER OR BOTH
ADEMCO 5881* Type RF RECEIVER
WIRELESS ZONES
5881L: UP TO 8
5881M: UP TO 16
5881H: UP TO 30
*5882 IN CANADA
ADEMCO 4219
WIRED EXPANSION MODULE
(8 ADD'L EOLR WIRED ZONES)
-OR-
ADEMCO 4229
WIRED EXPANSION/RELAY MODULE
(8 ADD'L EOLR WIRED ZONES PLUS 2
OUTPUT RELAYS)
-OR-
ADEMCO 4204 RELAY MODULE
(4 OUTPUT RELAYS)
BLK
RED
GRN
YEL
12345
678910
11 12 13 14 15
16 17 18 19 20
21 22 23 24 25
EARTH GROUND
SEE INSTRUCTIONS
FOR PROPER
GROUNDING
TELEPHONE WIRING
(VIA RJ31X
*
JACK AND DIRECT
CONNECT CORD)
*
CA38A IN CANADA
DOC LOAD NO.: 3
REMOTE KEYPADS
USE SL6150, SL6160RF
OR SL6160 KEYPADS
*
.
LOCAL PROGRAMMING
MUST BE DONE WITH AN
SL6160 CONNECTED TO
THE KEYPAD TERMINALS,
BUT NEED NOT REMAIN
IN THE SYSTEM.
OPTIONAL 4285 & 4286
PHONE MODULES
CONNECT TO PARTITION
1 KEYPAD TERMINALS.
(SEE INSTRUCTIONS).
BLACK: KEYPAD GROUND (–) RETURN
RED: KEYPAD PWR (+)
GREEN: DATA IN FROM KEYPAD
YELLOW: KEYPAD DATA OUT
REMOTE
KEYPAD
}
WARNING: TO PREVENT RISK OF SHOCK,
DISCONNECT TELEPHONE LINE AT TELCO JACK
BEFORE SERVICING THIS UNIT.
CHARGING VOLTAGE
13.8VDC
BATTERY
12V, 4AH MIN
+
+
CONNECTOR
TABS ON
BOARD
PLUG-IN TRANSFORMER
16.5VAC, 25VA (e.g. ADEMCO
No. 1321, USE No. 1321CN IN
CANADA)
TO 110VAC
UNSWITCHED
OUTLET (24HR)
+
BLK
RED
GRN
YEL
TO TERM 4
TO TERM 5
TO TERM 6
TO TERM 7
BLK
RED
GRN
YEL
AND/OR
SET RECEIVER’S
DIP SWITCH FOR
DEVICE ADDRESS
OF “0”. SEE
INSTRUCTIONS.
THIS EQUIPMENT SHOULD BE INSTALLED IN
ACCORDANCE WITH THE NATIONAL FIRE PROTECTION
ASSOCIATION’S STANDARD 72, CHAPTER 2 (NATIONAL
FIRE PROTECTION ASSOC., BATTERYMARCH PARK,
QUINCY, MA 02269). PRINTED INFORMATION
DESCRIBING PROPER INSTALLATION, OPERATION,
TESTING, MAINTENANCE, EVACUATION PLANNING
AND REPAIR SERVICE IS TO BE PROVIDED WITH THIS
EQUIPMENT.
RING
(GRAY)
TIP
(GREEN)
RING
(RED)
INCOMING
PHONE LINE
HANDSET
BLACK
RED
+
2000
OHMS
EOLR
2000
OHMS
EOLR
ZONE 1
ZONE 2
HI
LO
HI
LO
2000
OHMS
EOLR
2000
OHMS
EOLR
ZONE 3
ZONE 4
HI
LO
HI
LO
2000
OHMS
EOLR
2000
OHMS
EOLR
ZONE 5
ZONE 6
HI
LO
HI
LO
2000
OHMS
EOLR
2000
OHMS
EOLR
ZONE 7
ZONE 8
HI
LO
HI
LO
MAXIMUM LOOP RESISTANCE: (EACH ZONE) 300 OHMS
(PLUS EOLR)
RESPONSE, ZONES 1-8: 10, 350, OR 700 MSEC
(PROGRAMMABLE)
24 HR BATTERY STANDBY REQUIRED FOR FIRE
INSTALLATIONS. USE 12V, 17.2AH BATTERY
FOR 500mA AUX POWER. SEE INSTRUCTIONS.
BATTERY CAPACITY FOR EMERGENCY
BURGLARY STANDBY USE AT LEAST 4 HOURS.
BATTERY NORMALLY NEED NOT BE
REPLACED FOR AT LEAST 3 YRS.TO
DETERMINE TOTAL STANDBY LOAD
ON BATTERY, ADD 100mA TO TOTAL
OF AUX. POWER OUTPUT AND
REMOTE KEYPAD CURRENTS.
USE UL LISTED LIMITED
ENERGY CABLE FOR
ALL CONNECTIONS
BATTERY FUSE
FOR REPLACEMENT,
USE SAME VALUE
(e.g. ADEMCO No. 90-12)
9-PIN CONNECTOR
USED FOR 4300
TRANSFORMER
CONNECTIONS (FOR
OPTIONAL POWER LINE
CARRIER DEVICES)
SEE INSTRUCTIONS.
123456789
USE 4142TR CABLE
USE
4300 TRANSFORMER INTERFACE
IN PLACE OF 1321 WHEN POWER
LINE CARRIER DEVICES ARE BEING
USED (SEE INSTRUCTIONS FOR
CONNECTIONS)
TIP
(BROWN)
}
}
CAN BE USED FOR GLASS BREAK DETECTORS
–––––––––– OPTIONAL ––––––––––
5800TM
TRANSMITTER MODULE (20mA)
(for 5827BD Wireless Bidirectional
Keypad)
AND/OR
4285/4286 VOICE MODULE (160mA)
AND/OR
7720 PLUS/7820
LONG RANGE RADIO
MAY ALSO BE CONNECTED. SEE
INSTRUCTIONS ACCOMPANYING
THOSE DEVICES.
THIS DEVICE COMPLIES WITH PART 15 OF FCC RULES.
OPERATION IS SUBJECT TO THE FOLLOWING TWO
CONDITIONS: (1) THIS DEVICE MAY NOT CAUSE HARMFUL
INTERFERENCE, AND (2) THIS DEVICE MUST ACCEPT ANY
INTERFERENCE RECEIVED, INCLUDING INTERFERENCE
THAT MAY CAUSE UNDESIRED OPERATION.
COMPLIES WITH FCC RULES, PART 68.
FCC REGISTRATION NO. AC398U-68192-AL-E
RINGER EQUIVALENCE: 0.7B.
WEEKLY TESTING IS REQUIRED TO ENSURE
PROPER OPERATION OF THIS SYSTEM.
3A
ALARM OUTPUT
10.5-13.8VDC, 2A MAX. (600mA MAX.FOR UL USAGE,
INCLUDING AUX POWER)
STEADY FOR BURGLARY/PANIC, TEMPORAL PULSE
SOUNDING FOR FIRE (e.g. USE ADEMCO 702 SIREN,
OR 12V BELL). SEE INSTRUCTIONS.
CAN BE USED FOR 2-WIRE SMOKE DETECTORS
SET UNIT’S DIP
SWITCH FOR
DEVICE
ADDRESS
OF “1”.
SEE
INSTRUCTIONS.
FOR COMPLETE INFORMATION,
SEE INSTRUCTIONS
SMOKE
TO AUX PWR
OUTPUT
TERMINALS
+
-
TO HI SIDE OF SELECTED ZONE
TO LO SIDE OF SELECTED ZONE
+
-
-
+
EOL POWER
SUPERVISION
RELAY MODULE
A77-716B
5
4
4-WIRE SMOKE
OR COMBUSTION
DETECTOR
2000
OHMS
EOLR
HEAT
DETECTOR
ZONES 2–7
*
+
RED
BLK
VIOLET
*
IF PROGRAMMED FOR FIRE
RED JUMPER
CUT FOR BELL SUPERVISION.
ALSO, CONNECT 2000 OHM RESISTOR
DIRECTLY ACROSS SOUNDER.
SEALED LEAD-ACID
TYPE.
FOR CONNECTION OF OPTIONAL4285 OR 4286
PHONE MODULE TO PHONE TERMINALS, SEE
INSTRUCTIONS.
* If ordering keypads, order by Part No. as follows:
SL6150: Part No. 6150PL3
SL6150RF: Part No. 6150RFPL3
SL6160: Part No. 6160PL3
Figure 24. SL150 Summary of Connections