Section 17 -Output Device Programming
17–5
arming status of the system.
To program this, do the following:
1.
In
✱
80 Interactive mode, choose Output Device 01 and program
the Action (A) to be “2” (Close and stay closed). The Event you
want to start the Device action is a fault, so program 2 in (EV).
To use Zone List 1 for the 3 specific zones, program 1 in (ZL), and
program these 3 zones in
✱
81's Zone List 1.
2.
The second condition for turning on the indicator is triggering a
24-hour aux. zone (Zone Type 08). Therefore, program (ZT)
as 08.
3.
To stop the Device action and turn off the lamp, you do not
want to use a restore of any zone, so program a 0 for the
Restore of Zone List (ZL).
A manual entry of [User Code] + # + 8 + [Device No.] will be
used to turn off. Therefore, you do not need to program a Stop
event.
4.
Press
✱
to continue.
5.
The system will display a summary screen for the Start
programming for device 01. Press
✱
to continue.
6.
The system will display a summary screen for the Stop
programming for device 01. Press
✱
to continue.
7.
The system will display the
X10?
prompt. Enter 1 for yes.
8.
The
ENTER DEVICE No.
prompt for the next zone will be
displayed.
Press 00 and then [
✱
]
to exit the
✱
80 mode.
Now use
✱
81 Zone List mode to program the 3 specific zones in Zone
List 01.