SL150 Installation and Setup Guide
7–2
3. Connect the desired field wiring to the unit's relay contact terminals.
Supervision
4204 and 4229 modules are supervised against removal. CHECK and ZONE 09 will be
displayed if a module is disconnected from the control’s terminals (4, 5, 6, and 7). CHECK
and ZONE 09 will also be displayed if the module cover is removed and the tamper jumper is
installed.
BRN
GRN
BLK
(–) GROUND
RED
(+) 12VDC
YEL
4
3
2
1
ZONES
A
B
C
D
F
GH
DIP SWITCH FOR SETTING
ADDRESS AND ZONE A
RESPONSE TIME
TAMPER JUMPER
POSITION 229
IN CABINET
(NOT TAMPERED)
4229 REMOTE
(TAMPERED PROTECTED)
TB1
4229
TB2
WHT
GRY
VIO
BLK
YEL
ORG
NO
NC
C
GND
NO
NC
C
RLY
2
RLY
1
RELAYS SHOWN
DEENERGIZED
RELAY
CONNECTOR
RELAY
2
RELAY
1
(TERM 6)
(TERM 4)
(TERM 5)
(TERM 7)
NO C NC
TERMINALS ON
CONTROL PANEL
1
2
3
4
DATA OUT
TO CONTROL
DATA IN FROM
CONTROL
5
8
11
REED
(TAMPER)
SWITCH
2
E
1
3
4 6
7
9
10
12
TERMINATE EACH PROGRAMMED
ZONE WITH 1000 OHM (1K)
END-OF-LINE RESISTOR
(EACH ZONE'S LOOP RESISTANCE:
700-1300 OHMS)
4229 ADDRESS SETTINGS
SWITCH
NUMBER
("—" means "OFF")
0
1
123456789101112131415
2
ON
ON ON ON ON ON ON ON ON
3
ON ON ON ON ON ON ON ON
4
ON ON ON ON ON ON ON ON
5
ON ON ON ON ON ON ON ON
12345
OFF ON
4-PIN
CONSOLE
PLUG
EITHER OR BOTH
CAN BE USED
SWITCH SHOWN
FOR ADDRESS "0"
Figure 16. 4229 Connections to Control Panel